Home › CFD Handbook › Kv and Cv valve calculator
Kv and Cv calculator for control valves
Convert Kv, Kvs and Cv, size a control valve for a liquid and check it against choked flow.
Free calculator and guide · 25 min read · Updated November 2026
Calculator
Kv = 0.865 Cv; Av = Kv/36 000, in m²
Kv 11.3 · next catalogue Kvs 16
Water 20 °C · 8.00 m³/h at 0.50 bar · inlet 4.00 bar a · FL 0.90
Kv 11.3next catalogue Kvs 16
Cv 13.1Kvs 16 = Cv 18.570.6 % of Kvs used
Below the choked limit. Whether it cavitates depends on the valve’s xFz
Flow Q, m³/h
Drag the point to change the duty, or the Kvs pill to change the size
Pressure drop across the valve Δp, bar
Flow, % of fully open
Valve travel, %
in this circuitinherent
The valve on its own. Give the rest of the circuit to see how far it opens there and its authority.
Kv 11.3: what the duty needsKvs 16: the next catalogue valueCommon catalogue Kvs valuesCavitation from bar (your xFz)Choked from 3.22 bar: every line goes flat at this knee (FL 0.90)Flashing from bar: the outlet is below the vapour pressure (close to the duty’s pressure drop)Above the inlet pressure, 4.00 bar a: not possibleGive the inlet pressure to see the knee where the flow chokesThe duty shows on the map again when the inputs are in order.
Flow Q, m³/h
Drag the point to change the duty, or the Kvs pill to change the size
Pressure drop across the valve Δp, bar
Flow, % of fully open
Valve travel, %
in this circuitinherent
The valve on its own. Give the rest of the circuit to see how far it opens there and its authority.
Kv 11.3: what the duty needsKvs 16: the next catalogue valueCommon catalogue Kvs values (every second one)Cavitation from bar (your xFz)Choked from 3.22 bar: every line goes flat at this knee (FL 0.90)Flashing from bar: the outlet is below the vapour pressure (close to the duty’s pressure drop)Above the inlet pressure, 4.00 bar a: not possibleGive the inlet pressure to see the knee where the flow chokesThe duty shows on the map again when the inputs are in order.
Valve authority 0.56 with 0.20 bar in the rest of the circuit: the valve runs 91 % open and passes 80 % of its fully open flow there.
The duty needs Kv 11.3 (Cv 13.1). The next catalogue size, Kvs 16, is 70.6 % used and runs 91 % open with equal percentage trim. The flow chokes at a pressure drop of 3.22 bar for this inlet pressure and FL.
- Below the choked limit of 3.22 bar. Whether the valve cavitates depends on its xFz, which the valve maker gives.
- No valve inlet bore given: the valve Reynolds number, Kv/d² and the inlet velocity are not checked.
-
-
-
-
Key values
| Kv needed | 11.3 |
|---|---|
| Cv needed | 13.1 |
| Av needed | 3.14 × 10⁻⁴ m² |
| Chosen Kvs | 16 (Cv 18.5, Av 4.44 × 10⁻⁴ m²) |
| Share of Kvs used | 70.6 % |
| Size with a 10 % reserve | Kvs 16 |
| Catalogue sizes below and above | 10 / 25 |
| Flow, valve fully open | |
| Pressure drop, valve fully open | |
| Outlet pressure | 3.50 bar a |
| Vapour pressure | 0.0234 bar |
| Critical pressure ratio factor FF | 0.957 |
| Choked pressure drop | 3.22 bar |
| Pressure ratio xF | 0.13 |
| Pressure drop used for sizing | |
| By the plain formula, without the choked limit | |
| Cavitation factor xFz | |
| Pressure drop at xFz | |
| Valve authority | 0.56 |
| Pressure drop fully open at this flow | 0.25 bar |
| Flow fully open in this circuit | 9.98 m³/h |
| Travel, equal percentage | 91 % |
| Travel, linear | 70 % |
| Travel | |
| Share of the fully open flow | 80 % |
| Valve inlet bore | |
| Valve Reynolds number Rev | |
| Valve style modifier Fd, assumed for this type | |
| Loss coefficient K at the duty | |
| Loss coefficient K, valve fully open | |
| Velocity in the pipe bore | |
Kv = Q/√(Δp/G) with Q in m³/h and Δp in bar; Cv the same with Q in gpm and Δp in psi; G = ρ/1000 kg/m³; Kv = 0.865 Cv.
How the numbers were found
As a loss coefficient K
Give the pipe inner diameter to see the valve as a loss coefficient K.
Use this K in the pipe pressure drop calculator
Advanced
The valve is taken as line-size (FP = 1). With the bore the tool also checks the valve Reynolds number, Kv/d² and the inlet velocity.
Kv, Kvs and Cv: what they mean
Kv is the flow of water in cubic metres per hour (m³/h) that passes a valve at a pressure drop of 1 bar across it [1]. So Kv, the metric valve flow coefficient, is itself a flow: a valve with twice the Kv passes twice the water at the same pressure drop. For any other pressure drop, and for a liquid other than water, the calculator uses the relation behind the definition:
Kv = Q/√(Δp/G) (1)
Here Q is the flow in m³/h, Δp the pressure drop across the valve in bar and G the relative density of the liquid, its density divided by 1000 kg/m³. It is the turbulent, non-choked liquid equation of IEC 60534-2-1, eq. (1), written for Kv, m³/h and bar [2]. For water G is close to one, so the flow through a given opening rises with the square root of the pressure drop: four times the pressure drop gives twice the flow.
Kvs is the Kv of the fully open valve, at rated travel [3], and it is the number printed in the catalogue. The valve you order normally has a Kvs above the Kv your duty needs, so that it passes the duty before it is fully open [4]. Kv describes the duty, or the valve at one opening. Kvs describes the size.
Cv is the US counterpart: the flow of water at 60 °F in US gallons per minute that passes the valve at a pressure drop of 1 psi [5]. Masoneilan calls it the valve flow capacity coefficient [5]. Kv, Kvs and Cv are all valve flow coefficients: each is the water a valve passes at a fixed pressure drop, in its own units. One factor ties Kv and Cv:
Kv = 0.865 Cv (2)
A valve with Cv 50.0 therefore has Kv 43.3 [6]. Fisher lists Av beside Kv as a flow coefficient used outside North America [6]. In SI units it is defined by Q = Av√(Δp/ρ), with Q in m³/s, Δp in Pa and ρ in kg/m³ (our reading: the form that gives Fisher’s factor below). For a fluid of 1 kg/m³ at 1 Pa, Q = Av, and its unit is m². From the definitions, Av = Kv/36 000, about 2.78 × 10⁻⁵ Kv (our derivation), and Fisher gives Av = 2.40 × 10⁻⁵ Cv [6].
Kv is defined in IEC 60534-1 and in the German guideline VDI/VDE 2173, which makers cite for their Kvs values, and IEC 60534-2-3 holds the test procedures for flow capacity [7, 8, 9]. Sources disagree on the temperature of the test water: Siemens’s data sheets give a range [10], while KSB writes cold water [1], and so does this page.
Reading the Kv map
The calculator draws your duty on a Kv map: flow against the pressure drop across the valve, both on logarithmic axes. By (1) every Kv is then a straight line of slope one half, and the common catalogue Kvs values make a family of parallel lines, labelled with their Kvs and Cv at the right-hand edge. The line of the Kv your duty needs runs through the duty point, and the next catalogue Kvs is the first line above it. When the inlet pressure and the valve’s FL are known, every line goes flat at the same pressure drop, the knee where the flow chokes. You can drag the duty point, and the Kv and the size follow.
The numbers in the examples on this page are what the calculator shows when you load them. Like the default, the examples are constructed duties with our pick of FL for the valve type, not makers’ cases. The default is water at 20 °C, 8.00 m³/h with 0.50 bar across a post-guided globe valve and 4.00 bar a at the inlet. It needs Kv 11.3 (Cv 13.1, Av 3.14 × 10⁻⁴ m²), and the next catalogue value is Kvs 16.
Converting Cv to Kv
To convert Cv to Kv, multiply by 0.865, and to convert Kv to Cv, multiply by 1.156 [6]. Cv 50.0 is Kv 43.3, and Av 1.20 × 10⁻³ m².
Cv = 1.156 Kv, Av = Kv/36 000 (3)
If all you need is a conversion, type any one of the three into the “Convert” strip under “Find” and the other two follow. The strip opens on the Kv your duty needs, and the button “Use this Kv” sets the chosen Kvs from it. The strip, the result, the labels on the map and the working all use the same factor, 0.865.
In US units the makers write the same equation with Cv: Q = Cv√(Δp/G), with Q in US gallons per minute (gpm), Δp in psi and G the relative density, which they call the specific gravity [5, 6]. Set “Units” to US and you have a valve Cv calculator: gpm, psi and °F, with Cv first in the result. The default duty, 35.2 gpm at 7.25 psi, needs Cv 13.1.
You will meet other factors. Spirax Sarco rounds the pair to 1.16 and 0.87 [11]. Danfoss prints 0.86 and 1.17, which are not inverses of each other, and its 1.17 belongs to an older Kv that was defined with 1 kgf/cm² instead of 1 bar [11, 12]. The pure unit conversion, the US gallon per minute in m³/h divided by the square root of the psi in bar, is 0.86498 (our derivation). The two definitions also refer to slightly different water, so only three figures mean anything, and the calculator uses 0.865, the factor IEC 60534-2-1 gives in its Table 1 [2].
Note that Cv here is the US gallon figure. A Cv in imperial gallons is a different number, because the imperial gallon is the larger one [11], so check which one a data sheet gives before you convert it.
Sizing a control valve: the Kv you need
Sizing a control valve for a liquid means finding the Kv value that the duty needs from its flow and its pressure drop across the valve, and then choosing a catalogue Kvs, normally the next one above that Kv [2, 4]. Under “Find”, choose “Kv needed” and give the flow, the pressure drop and, for the choked-flow check, the inlet pressure. The calculator solves (1) for Kv and picks the next catalogue Kvs.
The default duty, 8.00 m³/h at 0.50 bar, needs Kv 11.3. Kvs 16 is the next catalogue value, and the duty uses 70.6 % of it. The two other modes under “Find” take the chosen Kvs as the valve fully open: “Flow” gives 11.3 m³/h through Kvs 16 at 0.50 bar, and “Pressure drop” gives 0.25 bar across it at 8.00 m³/h.
The calculator lists 21 common catalogue values from 0.1 to 1000. Each appears in Samson’s or Siemens’s tables [10, 13], but catalogues also hold values in between, such as 31.5 and 125 [10] or 60 and 360 [13], so you can type your own Kvs instead. A needed Kv below 0.1 or above 1000 gets a warning.
How much reserve to keep above the duty is practice, not a rule. Samson sizes motor-operated valves so that the largest calculated Kv is at most 0.9 of the Kvs, a reserve of 10 % [4]. Masoneilan asks for a valve that passes 10 to 15 % more than the specified maximum flow [5]. Siemens’s own worked example goes the other way: for a calculated Kv of about 26 it takes Kvs 25 rather than 30, because the smaller valve gives a somewhat larger authority [3]. The calculator names the next catalogue Kvs and the next one that keeps Samson’s reserve. In the default they are the same, Kvs 16.
In the example “Next size or the reserve” the duty is 12.0 m³/h at 0.60 bar, which needs Kv 15.5 (Cv 17.9). Kvs 16 would be used to 96.7 %, above Samson’s line, so the calculator adds Kvs 25 as the size with the reserve, used to 61.9 %. In the default circuit Kvs 16 would run 99 % open at this duty. It would still pass the flow, with almost nothing left. The calculator shows both sizes and leaves the choice to you.
Load the Next size or the reserve example in the calculator ↑
Choked flow and cavitation in control valves
Choked flow is the state in which a larger pressure drop across the valve gives no more flow [2]. For a liquid it starts at the choked pressure drop of IEC 60534-2-1, eqs. (3) and (4):
Δpchoked = FL2(p1 − FF pv), FF = 0.96 − 0.28√(pv/pc) (4)
Here p1 is the absolute inlet pressure, pv the vapour pressure of the liquid at the inlet temperature and pc its critical pressure, 22.064 MPa for water [14]. FF is 0.96 when the vapour pressure is near zero, and 0.957 for water at 20 °C. The standard sizes on the smaller of the actual and the choked pressure drop, its eq. (2) [2], and so does the calculator.
FL, the liquid pressure recovery factor, compares the flow a valve passes when it chokes with the flow the plain equation would give for the pressure drop from the inlet to the vena contracta inside the valve [2]. A value near one means the pressure recovers little after the vena contracta [15]. FL and Cv are matched sets that change with travel [2, 16], so use the maker’s value for your valve. For six valve types the calculator offers a typical value, our pick from Emerson’s tables, and shows the range those tables give over all the sizes they list [16]. Type the maker’s FL over our pick and the calculator keeps the other values of that type. For a butterfly valve that is not in the list, do the same with the butterfly type closest to its opening, so that the Reynolds number and velocity checks use butterfly values. For a valve of any other type, choose “Own valve” and type its FL. We left full-bore ball valves and angle valves out of the list, because we found no open source with their FL.
FL of one maker’s valves, from Emerson’s Control Valve Handbook [16]: the range over all the sizes listed and our pick of a typical value. For a real valve, use the maker’s value.
| Valve type | Typical FL, our pick | Picked from | Range in Emerson’s tables, all sizes |
|---|---|---|---|
| Globe valve, cage-guided (rated travel) | 0.84 | the middle of Emerson’s cage-guided rows | 0.77 to 0.88 |
| Globe valve, post-guided or small contoured plug (rated travel) | 0.90 | Emerson’s 1/2 in post-guided valve | 0.84 to 0.97 |
| Segmented (V-notch) ball valve, 60 degrees open | 0.82 | Emerson’s 8 in valve | 0.78 to 0.86 |
| Segmented (V-notch) ball valve, 90 degrees open | 0.62 | Emerson’s 4 in valve | 0.37 to 0.86 |
| High-performance butterfly valve, 60 degrees open | 0.69 | Emerson’s 4 in valve | 0.66 to 0.81 |
| High-performance butterfly valve, 90 degrees open | 0.53 | Emerson’s 4 in valve | 0.48 to 0.71 |
In the default case the duty takes 0.50 bar against a choked pressure drop of 3.22 bar. In the example “Choked”, water at 80 °C flows through a fully open segmented (V-notch) ball valve, Kvs 63 with FL 0.62, from 6.00 bar a to 1.50 bar a. It chokes at 2.13 bar (FF 0.947) and passes 93.4 m³/h. The plain formula, which takes the whole pressure drop of 4.50 bar, promises 136 m³/h, 45 % too much. Samson notes beside that formula that it leaves out the flow limit at critical conditions [4]. Near the knee a real valve does not turn as sharply as the map draws it. IEC 60534-8-4 puts incipient choked flow, where the flow first leaves the straight line (its Kc), roughly between FL3 and FL2 times (p1 − pv), and the beginning of choked flow at about FL2(p1 − pv) [17]. So the real curve bends before the knee, and the lower the FL, the earlier.
Load the Choked example in the calculator ↑
Flashing means the outlet pressure is at or below the vapour pressure, so vapour stays in the outlet pipe, and no valve can prevent it [16]. Once the pressure drop reaches the choked limit, flashing service is sized with the choked-flow equations [15]. In the example “Flashing”, water at 150 °C, with a vapour pressure of 4.76 bar, drops from 10.0 bar a to 3.00 bar a through a post-guided globe valve, FL 0.90. The drop is past the choked limit, so the calculator sizes on the choked pressure drop, 4.56 bar, and 20.0 m³/h needs Kv 8.97. The next catalogue value, Kvs 10, is used to 89.7 %. A liquid close to boiling can also flash before the drop reaches the choked limit. The calculator then says that the outlet flashes and sizes on the actual pressure drop, as eq. (2) of IEC 60534-2-1 does [2].
Load the Flashing example in the calculator ↑
Cavitation below the choked limit
A valve can cavitate before it chokes. Samson describes this with the pressure ratio xF = Δp/(p1 − pv): cavitation sets in when xF reaches xFz, a value for the valve and its opening that is found by noise measurement, and below xFz the valve does not cavitate [18]. xF is 0.13 in the default case. Note that Kc, the ratio at which the flow first leaves the square-root law, is not where cavitation begins, and Samson calls mixing the two up a serious mistake [18]. Masoneilan warns that FL is misleading as a limit for damaging cavitation [5].
So whether a duty cavitates depends on the valve, and the maker is the one to ask. We found no open source with typical xFz values for valve types, only Samson’s statement that ball valves allow cavitation-free control at the smallest pressure ratios, butterfly and rotary plug valves at somewhat higher ones and globe valves at the highest [18]. We therefore do not let the calculator guess. Without an xFz it says that the duty is below the choked limit and that whether it cavitates depends on the valve’s xFz, which the valve maker gives.
With the maker’s value typed under “Maker’s xFz at this opening and inlet pressure (optional)”, the map shades the band from xFz(p1 − pv) up to the knee, and the result says whether xF lies below or above it. Note that the value has to fit your duty. IEC 60534-8-4 gives xFz for an inlet pressure of 6 bar and corrects it for other inlet pressures [17], and the calculator applies no correction of its own. Samson adds that the comparison holds strictly only for liquids that behave like the test water [18], so for another liquid the calculator shows the result as a note, not as a verdict. To see it work, type 0.10, a deliberately low value chosen only to show the band and not a value for a globe valve. The band then starts at 0.40 bar, and the duty’s xF of 0.13 lies above it, so the result says that cavitation is expected.
Kv and the loss coefficient K
The loss coefficient K is the pressure drop of a fitting divided by the dynamic pressure of the flow in its bore, ρv2/2 [19]. Fisher calls it the resistance coefficient [6], and it is also called the K factor. Kv and K both say how much pressure a valve takes for a given flow, and the bore d ties them together:
K = 1.60 × 10⁻³ d4/Kv2, Kv = 0.0400 d2/√K (d in mm) (5)
This is our derivation, shown in full under How the calculator works. The density of the liquid cancels, and only the 1000 kg/m³ in the definition of Kv is left. KSB prints the same relation as ζ ≈ 16 d4/kv2 with d in centimetres [1], and the constant equals N2 of IEC 60534-2-1, 1.60 × 10⁻³ for Kv and millimetres [2]. With Cv and d in inches the constant is 890, as Fisher prints it, so K = 890 d4/Cv2 [6].
In the example “Kv to K”, Kvs 40 in a 50.0 mm bore is K = 6.25. At 0.50 bar it passes 28.3 m³/h, 4.00 m/s in the bore. K refers to the velocity in the bore you give, so for the pipe sum give the pipe’s inner diameter, the bore its friction term uses.
Open “As a loss coefficient K” at the end of the inputs and type that diameter. With “Kv needed” under “Find” it gives two values: K at the duty, from the Kv the duty needs, and K of the chosen Kvs fully open. With “Flow” or “Pressure drop” under “Find” the valve is fully open, so it gives one K, unless the valve chokes. In the default case, in a 50.0 mm bore, K at the duty is 78.2 and K of Kvs 16 fully open 39.0: at its duty opening the valve takes 0.50 bar, fully open only 0.25 bar. When the valve chokes, K at the duty is the K that gives the whole pressure drop across the valve at the duty flow, and it holds at that flow only. In the example “Choked”, with an 80.0 mm bore typed, that is K 34.8 for the 4.50 bar at 93.4 m³/h, while the fully open K of 16.5 gives only 2.13 bar.
The button “Use this K in the pipe pressure drop calculator” sends K at the duty with the duty flow to our Moody chart page. The pipe tool then shows the pressure drop the valve takes at your duty, added to the pipe’s friction and to any fittings you add from its table of minor losses and K values. It takes K up to 100 000. For a larger K the button opens it with the flow, the bore and the liquid but without the valve, and the line under the button tells you to add the valve’s pressure drop to the pipe’s result there. In both cases, when the outlet flashes, the line also says that the pipe after the valve carries liquid and vapour, which a liquid pipe calculation does not cover.
Load the Kv to K example in the calculator ↑
Kv in a network model
In Simcenter Flomaster a control valve for a liquid, its Incompressible Control Valve, is a loss coefficient K that changes with opening, referred to the valve’s nominal flow area. The typical curves it is supplied with come mostly from Miller, and its documentation asks for the maker’s curve where there is one [20]. It does not take a Kv for that valve directly. Its documentation gives the conversions from Kv, from Cv and from the SI coefficient Av to K, and notes that the US and imperial Cv are not the same quantity [20]. Because K there refers to the nominal flow area, work out a K for such a model on the valve’s nominal diameter (our reading of the two definitions).
With flow balancing it works the other way: you give the flow a branch needs and it finds the valve opening that delivers it [20]. Our post on flow balancing in Simcenter Flomaster shows the method, there for an orifice.
Its documentation also warns that ball, butterfly and gate valves do most of their throttling in the first 20 to 30 % of opening, so moving such a valve at a steady rate gives a highly non-linear change in flow and larger pressure changes than expected [20]. For a valve closed at a steady rate from fully open we read that as little change at first and then a fast one near the closed end, and a larger surge than expected. Our post on incompressible transients in Simcenter Flomaster shows how to set up such a run.
In Simcenter Amesim, the Two-Phase Flow library lets a restriction take its loss as Kv or Cv directly [21].
Inside the valve body, where the pressure falls below the vapour pressure, 3D CFD shows the cavity itself. Simcenter STAR-CCM+ models it as a Volume of Fluid flow with a cavitation model, and a transient run is the recommended set-up [22].
Valve authority
Valve authority is the pressure drop of the fully open valve at design flow divided by the total pressure drop of the part of the circuit whose flow it controls [3]:
N = Δpv100/(Δpv100 + Δpc) (6)
Here Δpv100 is the pressure drop of the fully open valve and Δpc that of the rest of the circuit in series with it, pipes, coils and fittings, both at the design flow. Type Δpc as “Pressure drop of the rest of the circuit”, and the opening panel beside the map shows how far the valve opens at your duty and its authority. In the default case the rest of the circuit takes 0.20 bar. Kvs 16 fully open would take 0.25 bar at 8.00 m³/h, so its authority is 0.56. An equal-percentage valve then runs 91 % open at the duty, a linear one 70 %.
The inherent characteristic is how Kv follows travel at a constant pressure drop. On an equal-percentage valve each equal step of travel changes Kv by the same percentage [23]: with a rangeability R of 50, by 48 % for every 10 % of travel. Rangeability is Kvs divided by Kvr, the smallest Kv at which the characteristic still holds [3], and Siemens gives typical values of 50 to over 150 [3]. We use R = 50 and draw the linear characteristic as a straight line from Kvr closed to Kvs fully open (our model). The travel the calculator gives is therefore that of an ideal characteristic: for a real valve, use the maker’s characteristic. Below Kvr the valve cannot control the flow: the calculator then gives no travel and suggests a smaller Kvs.
In the circuit the valve’s share of the pressure drop grows as it closes, so the installed characteristic, flow against travel, bends away from the inherent one, and the lower the authority, the more it bends. With an authority of one the two are the same [3]. The calculator works the installed curve out from N (our derivation, in full under How the calculator works). In the default case the duty flow is 80 % of what the circuit passes with the valve fully open. When the duty chokes or flashes, the calculator gives no authority and no installed curve. The derivation assumes that the valve’s pressure drop, like the circuit’s, grows with the square of the flow. Past the knee it does not, and a flashing outlet is two-phase, which the circuit model does not cover.
The sources do not agree on how much authority is enough. For a heating group with an injection circuit and a two-port valve, Siemens asks for at least 0.5 [3]. Spirax Sarco advises near 0.5 but not above it, so as not to raise the cost of pumping power, and certainly not below 0.2 [11]. A Danfoss data sheet gives 0.5 as ideal with 0.4–0.7 preferred [24]. Masoneilan’s working rule gives the valve about one third of the system’s pressure drop, and in very long lines or lines with a high pressure drop at least 15 %, up to 25 % where possible [5]. The calculator warns below 0.2, notes an authority below 0.5, and says nothing above it.
In the example “Low authority” the duty of “Next size or the reserve”, 12.0 m³/h at 0.60 bar, meets 0.50 bar of other losses and a Kvs 40 valve: two sizes above the Kvs 16 the duty needs, and one above the Kvs 25 that keeps Samson’s reserve. Its authority is 0.15, below the warning line, and it runs 76 % open at a duty flow of 73 % of the fully open flow.
The opening panel takes the pressure difference over valve and circuit as constant. With a pump whose head falls as the flow rises it is not, and our pump curve calculator finds where such a pump runs on its system.
How the calculator works
For a liquid the calculator uses the sizing equations of IEC 60534-2-1 for turbulent flow [2]. Under “Find” you choose the unknown: “Kv needed” solves (1) for Kv, “Flow” solves it for the flow through the chosen Kvs, and “Pressure drop” for the pressure drop across it. When the inlet pressure is known, the pressure drop in (1) is the sizing pressure drop, the smaller of the actual and the choked pressure drop of (4) [2]. With “Pressure drop” under “Find”, a flow above what the valve can pass when it chokes is refused, and the calculator gives that highest flow instead.
For water the calculator takes the density and the vapour pressure at the inlet temperature from IAPWS-IF97 and the viscosity from the IAPWS 2008 formulation, 0 to 350 °C [14, 25]. At 20 °C the vapour pressure is 0.0234 bar. Our air and water properties calculator gives the same values to the digits shown. For another liquid you type its density, and its vapour pressure and critical pressure for the choked-flow check. Without them the check does not run, and the result says so. The relative density G refers to 1000 kg/m³, as in the makers’ Kv equation. The standard refers it to water at 15 °C, 999.10 kg/m³, which moves Kv by 0.045 %, below the figures shown.
The calculator takes the valve to be the size of its pipe, so the piping geometry factor FP of IEC 60534-2-1 is 1, and the working says so. A valve smaller than its pipe sits between a reducer and an expander, which take part of the pressure drop and lower the flow at which the valve chokes. The standard corrects for them with FP and FLP, its eqs. (15) and (21) [2]. This version of the calculator does not apply them, so for such a valve take the result as the line-size case.
Under “Advanced” you can give the “Valve inlet bore (optional)”, and the calculator then runs three checks. It works out the valve Reynolds number of eq. (23) and warns below 10 000, where the turbulent equations no longer hold and the standard’s Reynolds number factor FR is needed [2], which the calculator does not apply. For the valve style modifier Fd in that number it takes Emerson’s value from the same row as our FL pick. The exception is cage-guided globe valves, where it takes 0.26, the lowest Fd in Emerson’s cage-guided rows: a lower Fd gives a lower Reynolds number and so the earlier warning [2, 16]. For “Own valve”, whose style the calculator does not know, it takes the same 0.26, which is also the lowest Fd in Emerson’s rows, so the warning comes early there too [16]. In the velocity check below it takes 10 m/s for that type, the limit Neles gives for segment, ball, globe and eccentric plug valves [15]. A typed FL alone changes neither: the calculator keeps the Fd and the velocity limit of the type you picked. The result shows the Fd it used.
The second check warns when Cv/d2 reaches 30 with d in inches, the limit Emerson gives for reasonable accuracy of the sizing equations [16]. In SI units the calculator tests the same line as Kv/d2 0.0402 with d in millimetres (our conversion). The third warns when the inlet velocity is above 10 m/s, or 7 m/s for butterfly valves, the limits Neles recommends for continuous liquid service [15]. Without the bore none of the three checks runs, and a liquid more viscous than 20 mm²/s, a threshold of our own, gets a note that its Reynolds number was not checked.
Our derivations, in full
Kv as a loss coefficient. By definition K = 2Δp/(ρv2). With Δp = (Q/Kv)2(ρ/ρ0) from (1), in bar, and v = Q/(πd2/4), ρ cancels and K = 2 × 10⁵ (π/4)2 36002 d4/(ρ0 Kv2) in SI units, with ρ0 = 1000 kg/m³ from the definition of Kv. With d in millimetres that is (5), K = 1.60 × 10⁻³ d4/Kv2 (our derivation).
Authority does not depend on the flow. With the valve fully open, its pressure drop and that of the rest of the circuit both grow with Q2, so N in (6) is the same at any flow, and the design flow only fixes the two values (our derivation).
The installed characteristic. Take the total pressure difference over valve and circuit as constant, and the circuit losses as growing with Q2. At relative travel h the valve has Φ = Kv/Kvs from its inherent characteristic, and the flow as a share of the fully open flow Q100 is Q/Q100 = 1/√(1 − N + N/Φ2). The inverse, Φ = √(N/(1/q2 − 1 + N)) with q = Q/Q100, gives the travel for the duty. N = 1 returns the inherent characteristic (our derivation).
Travel from Kv/Kvs. Equal percentage, Φ = Rh − 1, gives h = 1 + ln Φ/ln R. The linear model, Φ = 1/R + (1 − 1/R)h, gives h = (Φ − 1/R)/(1 − 1/R).
What the calculator does not do. It sizes liquids only, with no gas, steam or two-phase sizing beyond the flashing check. It does not apply the Reynolds number factor FR, so a viscous liquid or a very small flow needs the standard’s correction. It does not correct for reducers next to the valve. It judges cavitation only from the maker’s xFz, and it does not predict noise or damage.
References and changelog
References
[1] KSB SE & Co. KGaA, Centrifugal Pump Lexicon, article Head loss. www.ksb.com
[2] IEC 60534-2-1, Edition 2.0, 2011-03, Industrial-process control valves, Part 2-1: Flow capacity, Sizing equations for fluid flow under installed conditions. Cited by equation and table number only. webstore.iec.ch
[3] Siemens Switzerland Ltd, Knowledge: Hydronics in building systems, A6V11158658, 2025. cache.industry.siemens.com
[4] Samson AG, Application Notes AB 05 EN, KV coefficient: valve sizing, 2012. www.samsongroup.com
[5] Baker Hughes, Masoneilan Control Valve Sizing Handbook, Rev. C, 2022. dam.bakerhughes.com
[6] Emerson, Fisher Catalog 12, Section 2: ANSI/ISA/IEC Valve Sizing. www.emerson.com
[7] IEC 60534-1, Edition 4.0, 2023-05, Industrial-process control valves, Part 1: Control valve terminology and general considerations.
[8] VDI/VDE 2173:2022-08, Fluidic characteristic quantities of control valves and their determination (contents and sample pages). m.vdi.de
[9] IEC 60534-2-3, Edition 3.0, 2015-12, Industrial-process control valves, Part 2-3: Flow capacity, Test procedures.
[10] Siemens, data sheet A6V10794157, valves VVF42..C, 2024. sid.siemens.com
[11] Spirax Sarco, Learn about steam: Control valve sizing for water systems. www.spiraxsarco.com
[12] Danfoss, “kV: what, why, how, whence?”, H. Boysen and B. Strode, VF.HB.G3.02. assets.danfoss.com
[13] Samson AG, Information Sheet T 8000-3 EN, Flow coefficients for valves. www.samsongroup.com
[14] IAPWS R7-97(2012), Revised Release on the IAPWS Industrial Formulation 1997 for the Thermodynamic Properties of Water and Steam. iapws.org
[15] Valmet, Neles Flow Control Manual, 6th edition, 2022. www.valmet.com
[16] Emerson, Fisher Control Valve Handbook, sixth edition, D101881X012, 2023. www.emerson.com
[17] IEC 60534-8-4, Edition 3.0, 2015-09, Industrial-process control valves, Part 8-4: Noise considerations, Prediction of noise generated by hydrodynamic flow. Cited by equation number only.
[18] Samson AG, Technical Information L351 EN, Cavitation in Control Valves. www.samsongroup.com
[19] Hydraulic Institute Data Tool, Fluid Flow III-B, Frictional losses in valves, fittings, and bends (from the HI Engineering Data Book, 2nd edition, 1990). datatool.pumps.org
[20] Simcenter Flomaster documentation (2504), Siemens Digital Industries Software: Components Reference Manual, Incompressible Control Valve.
[21] Simcenter Amesim documentation (2604), Siemens Digital Industries Software: Two-Phase Flow library.
[22] Simcenter STAR-CCM+ documentation (2606), Siemens Digital Industries Software: Cavitation.
[23] Spirax Sarco, Learn about steam: Control valve characteristics. www.spiraxsarco.com
[24] Danfoss data sheet, seated valves VF 2, VL 2, VFS 2. assets.danfoss.com
[25] IAPWS R12-08, Release on the IAPWS Formulation 2008 for the Viscosity of Ordinary Water Substance, 2008. iapws.org
Changelog
November 2026: first published, with the calculator and this guide. Each cited statement was checked against the text of its source, and the Simcenter Flomaster, Simcenter Amesim and Simcenter STAR-CCM+ statements against the Siemens documentation. The IEC standards are cited by equation number from their official previews, and no text or table of them is reproduced. Relations marked “our derivation” are our own, and every example number is the calculator’s own result.
Related tools
All CFD Handbook tools →Hpump(Q) = Hsystem(Q)
Calculator
Pump curve and NPSH calculator
Find where a centrifugal pump runs on your system curve, the NPSH margin at that flow and the speed a new duty point needs.
Open calculator →
Δp = f (L/D) ρV²/2
Calculator
Pipe pressure drop calculator
Pressure drop and head loss of a pipe by Darcy–Weisbach, with the friction factor on a live Moody chart.
Open calculator →
ρ, μ, ν at T, p
Calculator
Air and water properties calculator
Density, viscosity, specific heat, conductivity and Prandtl number of dry air or liquid water at any temperature and pressure in the calculator’s range.
Open calculator →
Re = ρVD / μ
Calculator
Reynolds number calculator
The flow regime of a pipe, a duct, a plate, a cylinder or a sphere, with air and water properties at your temperature.
Open calculator →
Questions about Kv, Kvs and Cv

Questions about sizing a control valve, or about a whole piping system? We reply within one day.
Ask a technical question →
What is the Kv value of a valve?
Kv is the flow of water in m³/h that passes the valve at a pressure drop of 1 bar. It describes the valve at one opening, and Kvs is the Kv of the fully open valve, the number in the catalogue. For other pressure drops and liquids the flow follows Q = Kv√(Δp/G), so it rises with the square root of the pressure drop. To size a valve, you usually choose a Kvs above the Kv your duty needs.
How do I convert Cv to Kv?
Multiply Cv by 0.865 to get Kv, and multiply Kv by 1.156 to get Cv. Cv 50.0 is Kv 43.3. In the calculator, type either into the “Convert” strip under the “Find” row and the other follows, with Av, the SI coefficient. Note that this is the US Cv: a Cv in imperial gallons is a different number.
What is Kv in m³/h?
Kv is itself a flow in m³/h: the flow of cold water through the valve at a pressure drop of 1 bar. At another pressure drop the flow is Kv√(Δp/G) with Δp in bar, so a valve of Kvs 16 passes 11.3 m³/h of water at 0.50 bar. The US counterpart is Cv, in US gallons per minute at 1 psi.
Why do different Cv to Kv factors circulate?
Kv = 0.865 Cv and Cv = 1.156 Kv are the factors the IEC sizing standard uses. 1.16 and 0.87 are roundings of them. Danfoss prints 0.86 and 1.17, and 1.17 belongs to an older Kv defined with 1 kgf/cm² instead of 1 bar. The two definitions refer to slightly different water, so only three figures mean anything. The calculator uses 0.865 everywhere.
What Kvs should I order with a reserve?
A Kvs above the Kv the duty needs, and how far above is practice. Samson sizes motor-operated valves so that the largest calculated Kv is at most 0.9 Kvs, a 10 % reserve. In the example “Next size or the reserve”, 12.0 m³/h at 0.60 bar needs Kv 15.5, which would use 96.7 % of Kvs 16, so with the reserve the calculator names Kvs 25. It shows both sizes and leaves the choice to you.
What happens to the flow when a control valve chokes?
It stops rising. Past the choked pressure drop of IEC 60534-2-1, formula (4) on this page, a larger pressure drop across the valve gives no more flow, and the valve is sized on the choked pressure drop instead. In the example “Choked”, water at 80 °C flows through a fully open segmented (V-notch) ball valve from 6.00 bar a to 1.50 bar a. It chokes at 2.13 bar and passes 93.4 m³/h. The plain Kv formula with the whole 4.50 bar promises 136 m³/h, 45 % too much.
How do I get the flow in gpm from a valve’s Cv?
Cv is the flow in US gallons per minute at a pressure drop of 1 psi. At another pressure drop the flow is Cv√(Δp/G) in gpm, with Δp in psi and G the specific gravity of the liquid. So Kvs 16, which is Cv 18.5, passes 41.4 gpm of water at 5.00 psi. In the calculator, set “Units” to US and choose “Flow” under “Find” to get the flow through your valve in gpm.
Talk to an engineer in your region
Every Volupe business developer holds an engineering degree. Find your regional contact below, or send us a message.
Ask us about Kv and Cv valve calculator
Use this form for licence quotes, demos, training and technical questions.
What happens next
- A reply within one day.
- A scoping call with one of our engineers.
- A quote, demo or other next step that fits your enquiry.
After purchase: support from Volupe simulation engineers.